Toyota Corolla Cross Owners & Service Manuals

Toyota Corolla Cross: On-vehicle Inspection

ON-VEHICLE INSPECTION

CAUTION / NOTICE / HINT

HINT:

  • Steps 2 to 9 specify the procedure to determine the cause of a refrigerant leak.
  • Step 10 specifies the procedure to check if there is a clog in the expansion valve.

PROCEDURE

1. INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET

HINT:

The following examples show the readings of a manifold gauge set and the corresponding air conditioning system problems.

(a) Read the manifold gauge pressure when the following conditions are met:

  • Doors are fully open.
  • The engine is idling.
  • The A/C switch is on.
  • The temperature is set to max cool.
  • The blower speed is set to high.
  • Temperature at the air inlet with recirculate selected is 30 to 35°C (86 to 95°F).

(1) Normally functioning air conditioning system

Gauge Reading

Pressure Side

Refrigerant Volume

Low

150 to 250 kPa (1.5 to 2.5 kgf/cm2, 22 to 36 psi)

High

1370 to 1570 kPa (14.0 to 16.0 kgf/cm2, 199 to 228 psi)

(2) Abnormally functioning air conditioning system

  1. During operation, pressure on low pressure side cycles between normal and vacuum

    *a

    LO

    *b

    HI

    Symptom

    Air conditioning system periodically cools and then fails to cool

    Probable Cause

    Moisture in air conditioning system freezes at expansion valve orifice, causing refrigerant to temporarily stop circulating

    After system stops and warms up again, ice melts and normal operation is temporarily restored

    Diagnosis

    Cooler dryer (integrated into condenser tank) saturated with moisture

    Moisture in air conditioning system is freezing at expansion valve orifice and blocking circulation of refrigerant

    Corrective Actions

    Replace cooler dryer

    Remove moisture by repeatedly evacuating air from air conditioning system

    Recharge air conditioning system with proper amount of new or purified refrigerant

    HINT:

    For the example above, moisture is present in the air conditioning system.

  2. Pressure is low on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    Air conditioning system does not cool effectively

    Insufficient cooling performance

    Probable Cause

    Refrigerant leaks from air conditioning system

    Diagnosis

    Insufficient refrigerant

    Refrigerant leaking

    Corrective Actions

    Check for refrigerant leaks and repair if necessary

    Recharge air conditioning system with proper amount of new or purified refrigerant

    If gauges indicate pressure of close to 0, then it is necessary to evacuate air conditioning system after repairing leaks

    HINT:

    For the example above, there is insufficient refrigerant.

  3. Pressure is low on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    Air conditioning system does not cool effectively

    Frost exists on pipe from condenser to evaporator unit

    Probable Cause

    Refrigerant flow is obstructed by dirt inside pipes of condenser core

    Diagnosis

    Condenser is clogged

    Corrective Actions

    Replace condenser

    HINT:

    For the example above, there is poor circulation of refrigerant.

  4. Vacuum is indicated on low pressure side and very low pressure is indicated on high pressure side

    *a

    LO

    *b

    HI

    Symptom

    Air conditioning system does not cool effectively (system may cool occasionally)

    Frost or condensation is seen on piping on both sides of receiver/dryer or expansion valve

    Probable Cause

    Refrigerant flow is obstructed by moisture or dirt in air conditioning system

    Expansion valve is stuck closed

    Diagnosis

    Refrigerant does not circulate

    Corrective Actions

    Replace expansion valve

    Replace condenser

    Evacuate air conditioning system and recharge with proper amount of new or purified refrigerant

    HINT:

    For the example above, the refrigerant does not circulate.

  5. Pressure is too high on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    Air conditioning system does not cool effectively

    Probable Cause

    Unable to provide sufficient performance due to excessive amount of refrigerant

    Cooling effectiveness of condenser is insufficient

    Diagnosis

    Excessive amount of refrigerant in air conditioning system because excessive refrigerant was added during recharging

    Cooling effectiveness of condenser is insufficient because condenser fins are clogged or cooling fan is faulty

    Corrective Actions

    Clean condenser

    Check operation of condenser cooling fan

    If condenser is clean and fan operation is normal, check amount of refrigerant and recharge air conditioning system with proper amount of new or purified refrigerant

    HINT:

    For the example above, the air conditioning system is overcharged or cooling effectiveness of condenser is insufficient.

  6. Pressure is too high on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    Air conditioning system does not cool

    The low pressure piping is too hot to touch

    Probable Cause

    Air in air conditioning system

    Diagnosis

    Air present in air conditioning system

    Insufficient vacuum purging when evacuating air conditioning system

    Corrective Actions

    Replace cooler dryer

    Check compressor oil to see if it is dirty or insufficient

    Evacuate air conditioning system and recharge it with new or purified refrigerant

    NOTICE:

    These gauge indications occur when the air conditioning system has been left open and then recharged without evacuating the system.

    HINT:

    For the example above, air is present in the air conditioning system.

  7. Pressure is too high on both low and high pressure sides

    *a

    LO

    *b

    HI

    Symptom

    Air conditioning system does not cool effectively

    Frost or large amount of condensation on piping on low pressure side

    Probable Cause

    Expansion valve may be stuck open or metering refrigerant incorrectly

    Diagnosis

    Excessive refrigerant in low pressure piping

    Expansion valve open too wide

    Corrective Actions

    Replace expansion valve

    HINT:

    For the example above, there is an expansion valve malfunction.

  8. Pressure is too high on both low and high pressure sides or pressure is too low on high pressure side

    *a

    LO

    *b

    HI

    Symptom

    Air conditioning system does not cool effectively

    Probable Cause

    Internal leak in compressor

    Diagnosis

    Low compression

    Leak from damaged valve or other compressor component

    Corrective Actions

    Replace compressor

    HINT:

    For the example above, there is insufficient compressor compression.

(3) Gauge readings (Reference)

*a

Pressure on Low Pressure Side kPa (kgf/cm2, psi)

*b

Pressure on High Pressure Side kPa (kgf/cm2, psi)

*c

Blower High Zone

*d

Blower Low Zone

2. INSPECT LEAK INSPECTION PROCEDURE

HINT:

The following inspection specifies how to determine the cause of a refrigerant leak after determining the location of the leak using a gas leak detector. Use this procedure to determine where to clean and what to be replaced. Illustrations, specifications and part names are for reference only and may differ from the actual vehicle.

(a) Use a gas leak detector to inspect for refrigerant gas leaks.

*1

Compressor

*2

Evaporator

*3

Condenser

*4

Expansion Valve

*5

Rear Air Conditioning Unit

-

-

  • When leaking occurs around "A" parts in the illustration:

    Click here

  • When leaking occurs around "B" parts in the illustration:

    Click here

  • When leaking occurs around "C" parts in the illustration:

    Click here

  • When leaking occurs around "D" parts in the illustration:

    Click here

3. INSPECT EXPANSION VALVE AND PIPE FITTING AREA

NOTICE:

  • Do not reuse the O-rings once they are removed.
  • Make sure to complete the steps from a to h and replace all the parts in which defects are found.
  • If all the related parts are normal, foreign material may be temporarily adhering to the O-ring or there may be an airtight malfunction due to deformation.

(a) REMOVE PIPE:

NOTICE:

  • Wipe off the joint area with clean cloth before disassembly.
  • Slowly remove a pipe straight to prevent the sealing face from being damaged and foreign materials from dropping off.

(1) Remove the pipe from the expansion valve.

*1

Expansion Valve

*a

Pipes

(b) CHECK O-RING SURFACE IN PIPE:

NOTICE:

  • Check the O-ring surface in a well-lit place.
  • When it is difficult to check the surface condition due to oil adhesion, degrease the surface (such as by wiping it with a clean white cloth). Make sure not to lose any foreign material that was adhering to the surface.

(1) Check the entire O-ring surface and make sure that it is free from defects, such as damage (cuts, dents or crushed areas), foreign material adhesion or twists. If there is any defect, clean or replace the part.

Click here

*1

O-ring

(c) CHECK SEALING FACE OF PIPE:

NOTICE:

When removing the O-ring, use soft tools (such as tooth picks) to avoid damaging the sealing face or O-ring.

(1) Remove the O-ring.

(2) Check the entire pipe surface and make sure that it is free from defects, such as foreign material adhesion, damage or corrosion. If there is any defect, clean or replace the part.

Click here

*a

Sealing face

(d) CHECK SEALING FACE OF EXPANSION VALVE (PIPE SIDE):

NOTICE:

When it is difficult to check the surface condition due to oil adhesion, degrease the surface (such as by wiping it with a clean white cloth). Make sure not to lose any foreign material that was adhering to the surface.

(1) Check the entire sealing face of expansion valve (pipe side) and make sure that it is free from defects, such as foreign material adhesion, damage or corrosion. If there is any defect, clean or replace the part.

Click here

*a

Sealing face

(e) REMOVE EXPANSION VALVE:

NOTICE:

  • Wipe off the joint area with clean cloth before disassembly.
  • Slowly remove a pipe straight to prevent the sealing face from being damaged and foreign materials from dropping off.
  • When it is hard to remove, slowly sway up-and-down and right-to-left for removal.

(1) Remove the expansion valve from the evaporator.

HINT:

If necessary, remove the air conditioning unit.

Click here

*1

Evaporator

*2

Expansion Valve

(f) CHECK SEALING FACE OF EXPANSION VALVE (EVAPORATOR SIDE):

NOTICE:

When it is difficult to check the surface condition due to oil adhesion, degrease the surface (such as by wiping it with a clean white cloth). Make sure not to lose any foreign material that was adhering to the surface.

(1) Check the entire sealing face of expansion valve (evaporator side) and make sure that it is free from defects, such as foreign material adhesion, damage or corrosion. If there is any defect, clean or replace the part.

Click here

*a

Sealing face

(g) CHECK O-RING SURFACE IN EVAPORATOR:

NOTICE:

  • Check the O-ring surface in a well-lit place.
  • When it is difficult to check the surface condition due to oil adhesion, degrease the surface (such as by wiping it with a clean white cloth). Make sure not to lose any foreign material that was adhering to the surface.

(1) Check the entire O-ring surface and make sure that it is free from defects, such as damage (cuts, dents or crushed areas), foreign material adhesion or twists. If there is any defect, clean or replace the part.

Click here

*1

O-ring

(h) CHECK SEALING FACE OF EVAPORATOR:

NOTICE:

When removing the O-ring, use soft tools (such as tooth picks) to avoid damaging the sealing face or O-ring.

(1) Remove the O-ring.

(2) Check the entire evaporator surface and make sure that it is free from defects, such as foreign material adhesion, damage or corrosion. If there is any defect, clean or replace the part.

Click here

*a

Sealing face

4. INSPECT CONDENSER AND PIPE FITTING AREA

NOTICE:

  • Do not reuse the O-rings once they are removed.
  • Make sure to complete the steps from a to d and replace all the parts in which defects are found.
  • If all the related parts are normal, foreign material may be temporarily adhering to the O-ring or there may be an airtight malfunction due to deformation.

(a) REMOVE PIPE:

NOTICE:

  • Wipe off the joint area with clean cloth before disassembly.
  • Slowly remove a pipe straight to prevent the sealing face from being damaged and foreign materials from dropping off.

(1) Remove the pipes from the condenser.

*a

Discharge Side

*b

Liquid Side

(b) CHECK O-RING SURFACE IN PIPE:

NOTICE:

  • Check the O-ring surface in a well-lit place.
  • When it is difficult to check the surface condition due to oil adhesion, degrease the surface (such as by wiping it with a clean white cloth). Make sure not to lose any foreign material that was adhering to the surface.

(1) Check the entire O-ring surface and make sure that it is free from defects, such as damage (cuts, dents or crushed areas), foreign material adhesion or twists. If there is any defect, clean or replace the part.

Click here

*1

O-ring

(c) CHECK SEALING FACE OF PIPE:

NOTICE:

When removing the O-ring, use soft tools (such as tooth picks) to avoid damaging the sealing face or O-ring.

(1) Remove the O-ring.

(2) Check the entire pipe surface and make sure that it is free from defects, such as foreign material adhesion, damage or corrosion. If there is any defect, clean or replace the part.

Click here

*a

Seal Surface

(d) CHECK SEALING FACE OF CONDENSER:

NOTICE:

When it is difficult to check the surface condition due to oil adhesion, degrease the surface (such as by wiping it with a clean white cloth). Make sure not to lose any foreign material that was adhering to the surface.

(1) Check the entire sealing face of condenser and make sure that it is free from defects, such as foreign material adhesion, damage or corrosion. If there is any defect, clean or replace the part.

Click here

*a

Seal Surface

5. INSPECT COMPRESSOR AND PIPE FITTING AREA

NOTICE:

  • Do not reuse the O-rings once they are removed.
  • Make sure to complete the steps from a to d and replace all the parts in which defects are found.
  • If all the related parts are normal, foreign material may be temporarily adhering to the O-ring or there may be an airtight malfunction due to deformation.

(a) REMOVE PIPE:

NOTICE:

  • Wipe off the joint area with clean cloth before disassembly.
  • Slowly remove a pipe straight to prevent the sealing face from being damaged and foreign materials from dropping off.

(1) Remove the pipes from the compressor.

*a

Discharge Side

*b

Suction Side

(b) CHECK O-RING SURFACE IN PIPE:

NOTICE:

  • Check the O-ring surface in a well-lit place.
  • When it is difficult to check the surface condition due to oil adhesion, degrease the surface (such as by wiping it with a clean white cloth). Make sure not to lose any foreign material that was adhering to the surface.

(1) Check the entire O-ring surface and make sure that it is free from defects, such as damage (cuts, dents or crushed areas), foreign material adhesion or twists. If there is any defect, clean or replace the part.

Click here

*1

O-ring

(c) CHECK SEALING FACE OF PIPE:

NOTICE:

When removing the O-ring, use soft tools (such as tooth picks) to avoid damaging the sealing face or O-ring.

(1) Remove the O-ring.

(2) Check the entire pipe surface and make sure that it is free from defects, such as foreign material adhesion, damage or corrosion. If there is any defect, clean or replace the part.

Click here

*a

Sealing face

(d) CHECK SEALING FACE OF COMPRESSOR:

NOTICE:

When it is difficult to check the surface condition due to oil adhesion, degrease the surface (such as by wiping it with a clean white cloth). Make sure not to lose any foreign material that was adhering to the surface.

(1) Check the entire sealing face of compressor and make sure that it is free from defects, such as foreign material adhesion, damage or corrosion. If there is any defect, clean or replace the part.

Click here

*a

Sealing face

6. INSPECT OTHER AREA

NOTICE:

  • Do not reuse the O-rings once they are removed.
  • Make sure to check all the related parts and replace all the parts in which defects are found.
  • If all the related parts are normal, foreign material may be temporarily adhering to the O-ring or there may be an airtight malfunction due to deformation.
  • Check the following parts. Refer to other procedures for details.

(a) CHECK OTHER PART:

NOTICE:

  • Be sure there is sufficient light when checking the O-ring.
  • If the condition of the surface is difficult to see, degrease it so it is easier to see. However, be careful when degreasing it so that any foreign matter that is attached to it is not misplaced.

(1) Check the O-ring surface of the pipe or part.

Click here

*1

O-ring

(2) Check the sealing face of the pipe.

Click here

*a

Sealing face

(3) Check the sealing face of the part.

Click here

*a

Sealing face

7. INSPECT O-RING ABNORMALITY

(a) Check the O-ring for any abnormalities.

*a

OK condition

*b

There are no cuts, dents, crushed areas, foreign material or twists

*c

Cut

*d

Dent/Crushed Area

*e

Foreign Material

*f

Twist

*g

Metal fragment

*h

Resin fragment

*i

Lint

*j

Hair

8. INSPECT SEALING FACE ABNORMALITY (O-RING ATTACHED AREA)

(a) Check the seal surface of the O-ring mount for any abnormalities.

*a

OK condition

*b

Processing evidence in circumferential direction is NOT a cause of leakage.

*c

Foreign Material

*d

Damage

*e

Corrosion

*f

Metal fragment

*g

Resin fragment

*h

Lint

*i

Hair

*j

White and yellow materials adhered (corrosion product)

*k

Damage (scratches) in axial direction and discoloration (black)

-

-

9. INSPECT SEALING FACE ABNORMALITY (PART JOINTED AREA)

(a) Check the seal surface of the connector for any abnormalities.

*a

OK condition

*b

Processing evidence in circumferential direction is NOT a cause of leakage.

*c

Foreign Material

*d

Damage

*e

Corrosion

*f

Metal fragment

*g

Resin fragment

*h

Lint

*i

Hair

*j

Uneven discoloration (black) on sealing face

10. INSPECT FOR FAULTY EXPANSION VALVE

(a) Recover refrigerant

(1) Connect the refrigerant recovery valve and recover the refrigerant.

NOTICE:

  • Perform this procedure in accordance with the repair manual for each vehicle.
  • Use the refrigerant recovery unit in accordance with the manufacturer's instruction manual.

(b) Install air conditioner service tool set

(1) Install the air conditioner service tool set to the vehicle (high pressure side).

SST: 09985-20010

(2) Open all the valves of the air conditioner service tool set.

(3) Install the refrigerant recovery unit or vacuum pump to the vehicle (low pressure side).

Connection Conditions:

Tool

Connected to

Air conditioner service tool set (High pressure hose)

Vehicle (High pressure side)

Air conditioner service tool set (Center hose)

-

Air conditioner service tool set (Low pressure hose)

-

Refrigerant recovery unit or vacuum pump

Vehicle (Low pressure side)

(c) Inspect expansion valve

(1) Depending on the type of low pressure side hose of the air conditioner service tool set, prevent air from being drawn in as shown in the illustration.

*A

With Attachment

*B

Without Attachment

*C

With Intermediate Valve

-

-

*a

Block the end of the hose with your thumb.

*b

Close the intermediate valve.

(2) While maintaining the above state, check that the gauge on the low pressure side changes when the center hose is closed and opened as shown in the illustration.

Result:

Result

Judgement

The gauge indicates a negative pressure (approximately -50 kPa (-0.5 kgf/cm2, -7.3 psi)).

Expansion valve is normal.

The indicated gauge pressure does not change.

Expansion valve is abnormal.

    READ NEXT:

     Replacement

    REPLACEMENT PROCEDURE 1. RECOVER REFRIGERANT FROM REFRIGERATION SYSTEM (a) Turn the ignition switch ON. (b) Operate the compressor under the conditions shown below: Item Condition Op

     Refrigerant Line

     Components

    COMPONENTS ILLUSTRATION *A for Gasoline Model - - *1 PIPING CLAMP *2 SUCTION PIPE SUB-ASSEMBLY *3 SUCTION HOSE SUB-ASSEMBLY *4 DISCHARGE HOSE SU

    SEE MORE:

     Terminals Of Ecu

    TERMINALS OF ECU REAR TELEVISION CAMERA ASSEMBLY (a) Disconnect the rear television camera assembly connector. (b) Measure the voltage on the wire harness side connector according to the value(s) in the table below. Terminal No. (Symbol) Terminal Description

     Lost Communication with ECM/PCM "A" Missing Message (U010087,U012687,U012987,U014087,U016387,U029387)

    DESCRIPTION These DTCs are stored if there is a malfunction in the CAN communication system connected to the parking assist ECU. HINT: If CAN communication system DTCs are stored, they may also be stored in other systems. DTC No. Detection Item DTC Detection

    © 2020-2024 Copyright www.tcorollacross.com