DESCRIPTION
If none of the switch indicators on the air conditioning control assembly illuminate, the following factors may be the cause.
Symptom | Factor |
---|---|
A/C switch indicator does not illuminate |
|
PROCEDURE
1. |
CHECK MALFUNCTION STATUS |
(a) Check the malfunction status of switch indicators on the air conditioning control assembly.
Result | Proceed to |
---|---|
Indicators are not always illuminated |
A |
Indicators are not illuminated only immediately after starting the engine |
B |
B | GO TO INITIALIZATION |
|
2. |
READ VALUE USING GTS |
(a) Read the Data List according to the display on the GTS.
Body Electrical > Air Conditioner > Data List
Tester Display | Measurement Item |
Range | Normal Condition |
Diagnostic Note |
---|---|---|---|---|
Ambient Temperature Sensor |
Thermistor assembly | Min.: -327.68°C (-557.82°F) Max.: 327.67°C (-621.81°F) |
Actual ambient temperature displayed |
Ambient temperature sensor (thermistor assembly) circuit malfunction |
Tester Display |
---|
Ambient Temperature Sensor |
OK:
The value displayed is 0°C (32°F) or higher.
OK | INSPECT REFRIGERANT PRESSURE WITH MANIFOLD GAUGE SET |
NG | GO TO OTHER DIAGNOSIS PROCEDURE (Ambient Temperature Display System) |